MHSC Lighting completed a full LED lighting conversion analysis for four Wylie ISD campuses: Wylie High School, Wylie West Intermediate School, Wylie West Elementary School and Wylie West Early Childhood Center. Every classroom, hallway, gym, cafeteria, office, parking lot and athletic building was audited fixture by fixture. Replacing outdated T-12, T-8 and T-5 fluorescent, CFL and metal halide lighting with LED cuts the district’s lighting energy use by about 68%.
Projected annual electricity savings
Electricity saved per year
Lighting demand reduced
Reduction in lighting energy use
Download the full Wylie ISD white paper
Wylie ISD LED Lighting Conversion: A Four-Campus Energy Savings White Paper (PDF). Campus-by-campus results, methodology, before and after photos, 3D design renders and 10-year savings.
Campus-by-Campus LED Savings
| Campus | Current lighting cost / year | LED lighting cost / year | Annual savings | kWh saved / year | Reduction |
|---|---|---|---|---|---|
| Wylie High School | $122,192 | $38,988 | $83,204 | 614,054 | 68.1% |
| Wylie West Intermediate School | $43,758 | $12,960 | $30,798 | 227,290 | 70.4% |
| Wylie West Elementary School | $45,707 | $15,094 | $30,612 | 225,922 | 67.0% |
| Wylie West Early Childhood Center | $31,127 | $10,175 | $20,951 | 183,782 | 67.3% |
| Total, 4 campuses | $242,784 | $77,217 | $165,565 | 1,251,048 | 68.2% |
Before & After: Wylie High School LED Upgrade
The new LED fixtures give brighter, more even light across the commons, cafeteria, gymnasium and indoor athletic facility, with no flicker, no warm-up delay and a cleaner 4000K–5000K color that makes spaces feel open and safe.




Project Highlights by Campus
Wylie High School: $83,204 per year
The largest campus in the project covers academic wings, the performing arts center, the Ag building and shop, the bus barn, the fitness center, the Dawg House indoor athletic facility, the press box and the stadium visitor side.
- Gymnasiums and indoor athletics: 6-lamp and 4-lamp T5 high bays replaced with 110W and 160W LED high bays.
- Classroom wings: more than 600 4-lamp T-8 troffers in the 200, 300 and 400 sections and Hall 600 converted to 2-lamp, 20W LED tubes.
- Parking and back drive: 1,000W and 400W metal halide shoebox poles, street lights and floods replaced with 200W–300W LED area lights.
- Older T-12 areas: offices, the library, the computer lab and portable buildings moved off obsolete T-12 lamps.
Wylie West Intermediate School: $30,798 per year
The highest percentage reduction of the four campuses at 70.4%.
- 34 6-lamp T5 gym high bays replaced with 160W LED high bays, including emergency-backup fixtures.
- More than 350 classroom and hallway troffers converted to LED, including Rooms 1–28 and the 300-wing classrooms.
- Metal halide parking lot poles and outdoor soffit lighting upgraded to LED.
Wylie West Elementary School: $30,612 per year
- 1,000W metal halide parking lot poles replaced with 300W LED area lights, the biggest single savings item on campus.
- Big gym and small gym T5 high bays replaced with 160W and 110W LED high bays.
- Kitchen and office troffers replaced with 40W LED flat panels. Classrooms, the library, the cafeteria and the stage converted to LED tubes and lamps.
Wylie West Early Childhood Center: $20,951 per year
- Nearly 400 3-lamp T-8 troffers in classrooms, halls and kindergarten rooms converted to 10.5W LED tubes.
- Gym T5HO high bays replaced with 110W LED high bays.
- Exterior metal halide wall packs, ground lights and parking poles replaced with LED for better safety at drop-off and pickup.
What Was Replaced
- T-12 and T-8 fluorescent troffers and strips → 10.5W and 20W LED T8 tubes, often cutting 4-lamp fixtures down to 2 lamps
- T5 and T5HO high bays in gyms and athletic buildings → 110W and 160W LED high bays
- Metal halide shoebox poles, street lights, floods and wall packs → 40W–300W LED area, flood and wall pack fixtures
- CFL, PAR38, BR30 and incandescent recessed cans and lamps → plug-in LED and LED lamps
- Emergency battery-backup fixtures kept code-compliant with LED emergency driver kits
- Fixtures that were already LED were left in place, so the district only pays for what it needs
How the Savings Were Calculated
Each fixture’s existing wattage, including ballast load, was compared with its LED replacement. Interior lighting was calculated at 14 hours per day over 196 school days. Exterior and parking lighting was calculated at 12 hours per night, 365 days a year. Costs use each campus’s utility rate: $0.1355/kWh for the high school, intermediate and elementary campuses, and $0.1140/kWh for the early childhood center. Figures are projections from MHSC’s LED conversion analysis and do not include maintenance savings from longer-life LED products.
Frequently Asked Questions
How much can a school district save by switching to LED lighting?
Across these four Wylie ISD campuses, converting to LED is projected to cut lighting electricity costs from $242,784 to $77,217 per year, a savings of $165,565 annually, or about 68%.
Which areas of a school save the most with LED?
Large classroom wings with hundreds of fluorescent troffers, gymnasiums with T5 high bays, and parking lots with 400W–1,000W metal halide poles produce the biggest savings, because they have the most fixtures or the highest wattage and the longest run times.
Does MHSC Lighting audit the whole campus?
Yes. MHSC documents every fixture by location, type, lamp count and wattage, then matches it with the right LED replacement and calculates the cost and energy savings room by room. Areas that are already LED are excluded.
Planning an LED Upgrade for Your School District?
Get a free lighting and electrical audit with a campus-by-campus savings breakdown like this one, or download the full Wylie ISD white paper (PDF).
More Wylie projects: read about the Wylie High School indoor field lighting design and the Wylie tennis court LED lighting project, or browse all of our school district and university projects.